Compare design CFM against measured CFM per branch.
Enter your values
Enter the design airflow in CFM.
Enter the measured airflow in CFM.
Results update instantly as you type — no submit needed. Your values are remembered on this device, and the shareable link reopens the calculator with exactly these numbers.
- Percent of design
- 78.7%
- Difference
- -32 CFM
- Action
- Open damper or check restriction
- Target band
- 135–165 CFM
Quick answer
A branch is considered balanced when measured airflow sits within 10% of its design value.
% of design = measured / design x 100
At a glance
| What it does | Compare design CFM against measured CFM per branch. |
|---|---|
| Category | HVAC & Airflow |
| Inputs needed | Design airflow, Measured airflow |
| Main output | Percent of design |
| Formula | % of design = measured / design x 100 |
| Cost | Free — no sign-up, no download |
How to use the Air Balance Calculator
- 1Record the design airflow for the branch from the duct drawing.
- 2Measure the delivered airflow with a flow hood or traverse.
- 3Adjust the balancing damper and re-measure.
Inputs explained
- Design airflow(CFM)
- Enter the design airflow in CFM.
- Measured airflow(CFM)
- Enter the measured airflow in CFM.
Worked example
Using the values the calculator loads with:
Inputs
- Design airflow150 CFM
- Measured airflow118 CFM
Results
- Percent of design78.7%
- Difference-32 CFM
- ActionOpen damper or check restriction
- Target band135–165 CFM
Frequently asked questions
What tolerance is acceptable?
Most specifications allow plus or minus 10% on each branch and 5% on the system total.
Should I balance with a dirty filter?
No — fit a clean filter first, otherwise every reading shifts once it is changed.
What do I need to enter into the Air Balance Calculator?
Just 2 values: design airflow, measured airflow. Every field starts with a realistic example, so you can change one number at a time and watch the result update instantly.
How does the Air Balance Calculator work out the answer?
A branch is considered balanced when measured airflow sits within 10% of its design value. It applies the formula % of design = measured / design x 100 and shows the working so you can check each step by hand.
Is the Air Balance Calculator free, and do I need an account?
It is completely free with no sign-up, no download and no usage limit. Everything is calculated in your browser, so the numbers you type never leave your device.