Wire Voltage Drop Calculator
Voltage drop over a wire run by length and gauge.
Reviewed by the Calculation Machine team · Updated 24 October 2026 · How we check our maths
Your values
ⓘ Live results
- Voltage drop
- 3.14 V
- Percent drop
- 2.62%
- Voltage at load
- 116.86 V
- Status
- Within recommended 3% limit
Quick answer
Voltage drop in a two-wire circuit is Vdrop = 2 × one-way length × current × resistance per foot, because current flows out and back. A 50 ft run carrying 10 A in 14 AWG copper (3.14 Ω per 1,000 ft) drops 3.14 V, which is 2.62% of 120 V — inside the common 3% guideline for branch circuits.
What the Wire Voltage Drop calculator does
This calculator finds the voltage lost along a wire run, that loss as a percentage of the supply, and the voltage left at the load. It flags whether the drop is within the widely used 3% guideline.
It is used when running power to a detached garage, shed, well pump or EV charger; laying low-voltage landscape lighting; and wiring 12 V solar, RV and marine systems, where a volt or two matters far more. Too much drop makes motors run hot, lights dim and electronics reset.
You need the wire's resistance per 1,000 ft, which depends on gauge and material; the table on this page lists common copper sizes. The method treats the run as a single-phase or DC circuit with a supply and return conductor. Once you know the drop is acceptable, confirm the wire can carry the current safely with the wire gauge ampacity calculator.
The formula
Vdrop = 2 × L × I × R ÷ 1,000 % drop = Vdrop ÷ Vsupply × 100
| Symbol | Meaning | Unit |
|---|---|---|
| L | One-way length of the run, from supply to load | ft |
| I | Load current | A |
| R | Conductor resistance per 1,000 ft | Ω/1,000 ft |
| 2 | Accounts for both the outgoing and return conductors | — |
| Vsupply | Voltage at the start of the run | V |
Resistance values come from NEC Chapter 9, Table 8 (DC resistance at 75 °C). For balanced three-phase circuits, replace the 2 with √3 (1.732). For large AC conductors (roughly 1/0 and above), reactance adds to the drop and NEC Table 9 values give a more accurate answer. The NEC's 3% branch / 5% total figure is an informational recommendation for efficiency, not a mandatory rule, though some local codes and equipment makers require it.
Worked examples
Garage outlet circuit at 120 V
A 50 ft run of 14 AWG stranded copper (3.14 Ω per 1,000 ft) feeding a 10 A load.
Inputs
- One-way length50 ft
- Current10 A
- Resistance per 1000 ft3.14 ohms (12 AWG copper default)
- Supply voltage120 V
Result
- Voltage drop3.14 V
- Percent drop2.62%
- Voltage at load116.86 V
- StatusWithin recommended 3% limit
2.62% is within the 3% guideline. Pushing the same circuit to its full 15 A would raise the drop to about 3.9%, so 12 AWG is the safer choice for a run this long.
Long 240 V run to a workshop
A 150 ft run of 12 AWG stranded copper (1.98 Ω per 1,000 ft) carrying 16 A for a 240 V compressor.
Inputs
- One-way length150 ft
- Current16 A
- Resistance per 1000 ft1.98 ohms (12 AWG copper default)
- Supply voltage240 V
Result
- Voltage drop9.5 V
- Percent drop3.96%
- Voltage at load230.5 V
- StatusExceeds recommended 3% limit
3.96% exceeds the guideline. Stepping up to 10 AWG (1.24 Ω per 1,000 ft) cuts the drop to about 2.5%, and motor starting current would otherwise cause a much bigger momentary sag.
12 V solar or RV circuit
A 20 ft run of 10 AWG copper (1.24 Ω per 1,000 ft) carrying 15 A from a 12 V battery to a fridge.
Inputs
- One-way length20 ft
- Current15 A
- Resistance per 1000 ft1.24 ohms (12 AWG copper default)
- Supply voltage12 V
Result
- Voltage drop0.74 V
- Percent drop6.2%
- Voltage at load11.26 V
- StatusExceeds recommended 3% limit
Only 0.74 V is lost, but that is 6.2% of 12 V, enough to trip a fridge's low-voltage cutout. Low-voltage DC runs usually need much thicker wire than mains runs of the same length.
Copper wire resistance per 1,000 ft by AWG
DC resistance of uncoated stranded copper at 75 °C, from NEC Chapter 9, Table 8. Aluminum conductors have roughly 1.6 times the resistance of copper at the same gauge.
| AWG | Ω per 1,000 ft | Ω per km | Typical use |
|---|---|---|---|
| 14 | 3.14 | 10.3 | 15 A lighting and outlets |
| 12 | 1.98 | 6.5 | 20 A outlets, kitchens |
| 10 | 1.24 | 4.1 | 30 A dryers, water heaters |
| 8 | 0.778 | 2.55 | 40 A ranges, subpanels |
| 6 | 0.491 | 1.61 | 55 A feeders, EV chargers |
| 4 | 0.308 | 1.01 | Larger feeders |
| 2 | 0.194 | 0.64 | Service and subpanel feeders |
How much voltage drop is acceptable
- Mains branch circuits: 3% on the branch and 5% in total from service to outlet, per the NEC's informational notes. In the UK, BS 7671 sets maximum drops of 3% for lighting and 5% for other uses on installations supplied from the public network.
- Motors: large drops reduce starting torque and raise running current and temperature. Manufacturers often require supply voltage within ±10% of nameplate.
- Low-voltage DC (12/24 V): ABYC marine practice uses 3% for critical circuits such as navigation lights and electronics and 10% for less critical loads.
- Long runs at 120 V: if a run is long, moving the load to 240 V halves the current and quarters the percentage drop for the same power.
Fixing too much voltage drop
The three levers are thicker wire, a shorter run or a higher voltage. Each step down of three AWG numbers roughly halves resistance, so going from 14 AWG to 10 AWG cuts the drop by about 60%. The wire gauge calculator can suggest a gauge directly from length and allowed drop. Remember that ampacity and voltage drop are separate checks: a wire can be safe for its current and still lose too much voltage over a long run.
How to use the Wire Voltage Drop Calculator
- 1Measure the one-way distance along the cable route from the panel or battery to the load, not the straight-line distance.
- 2Enter the load current from the device's nameplate, or the breaker rating for a worst-case check.
- 3Enter the wire's resistance per 1,000 ft from the table above (the default 3.14 is 14 AWG stranded copper).
- 4Enter the supply voltage and read the drop, percentage and voltage at the load.
Frequently asked questions
What is the maximum voltage drop allowed?
The NEC recommends no more than 3% on a branch circuit and 5% overall, but treats this as guidance rather than a requirement. Some jurisdictions and equipment, such as fire pumps, have mandatory limits.
Why is the length multiplied by 2?
Current flows out on one conductor and back on the other, so the total wire length carrying current is twice the one-way distance.
What size wire do I need for 100 ft at 20 A on 120 V?
12 AWG gives about 7.9 V or 6.6% drop, which is too much. 10 AWG gives about 4.1% and 8 AWG about 2.6%, so 8 AWG meets the 3% guideline.
Does voltage drop waste electricity?
Yes. The lost voltage times the current is power turned into heat in the wire — 3.14 V at 10 A is about 31 W in the garage example.
How do I calculate voltage drop for three-phase?
Use √3 (1.732) instead of 2: Vdrop = 1.732 × L × I × R ÷ 1,000, then divide by the line-to-line voltage for the percentage.
References
- NFPA 70, National Electrical Code (Chapter 9, Tables 8 and 9) — National Fire Protection Association (NFPA)
- BS 7671: Requirements for Electrical Installations (IET Wiring Regulations) — Institution of Engineering and Technology (IET) / BSI
- ABYC E-11: AC and DC Electrical Systems on Boats — American Boat and Yacht Council (ABYC)