HVAC & Airflow

Data Center CFM per kW Calculator

Rack airflow from IT load and delta T.

Enter your values

Enter the it load in kW.

Enter the temperature rise in °F.

Enter the number of racks you are working with.

Results update instantly as you type — no submit needed. Your values are remembered on this device, and the shareable link reopens the calculator with exactly these numbers.

Results
CFM per kW
158
Airflow per rack
1,264 CFM
Total room airflow
12,637 CFM
Total IT load
80 kW
Cooling required
22.7 tons

Quick answer

IT equipment needs roughly 126 CFM per kW at a 20°F rise, scaling inversely with the delta T you design for.

CFM = kW x 3412 / (1.08 x ΔT °F)

At a glance

What it doesRack airflow from IT load and delta T.
CategoryHVAC & Airflow
Inputs neededIT load, Temperature rise, Number of racks
Main outputCFM per kW
FormulaCFM = kW x 3412 / (1.08 x ΔT °F)
CostFree — no sign-up, no download

How to use the Data Center CFM per kW Calculator

  1. 1Enter the average IT load per rack in kW.
  2. 2Choose the delta T across the equipment — 20°F is common, 30°F for containment designs.
  3. 3Make sure the CRAC units can deliver the total airflow, not just the tonnage.

Inputs explained

IT load(kW)
Enter the it load in kW.
Temperature rise(°F)
Enter the temperature rise in °F.
Number of racks
Enter the number of racks you are working with.

Worked example

Using the values the calculator loads with:

Inputs

  • IT load8 kW
  • Temperature rise20 °F
  • Number of racks10

Results

  • CFM per kW158
  • Airflow per rack1,264 CFM
  • Total room airflow12,637 CFM
  • Total IT load80 kW
  • Cooling required22.7 tons

Frequently asked questions

Why does delta T matter so much?

Raising delta T from 20 to 30°F cuts required airflow by a third, saving large amounts of fan energy.

Containment?

Hot or cold aisle containment prevents recirculation and lets you run higher supply temperatures.

What do I need to enter into the Data Center CFM per kW Calculator?

Just 3 values: it load, temperature rise, number of racks. Every field starts with a realistic example, so you can change one number at a time and watch the result update instantly.

How does the Data Center CFM per kW Calculator work out the answer?

IT equipment needs roughly 126 CFM per kW at a 20°F rise, scaling inversely with the delta T you design for. It applies the formula CFM = kW x 3412 / (1.08 x ΔT °F) and shows the working so you can check each step by hand.

Is the Data Center CFM per kW Calculator free, and do I need an account?

It is completely free with no sign-up, no download and no usage limit. Everything is calculated in your browser, so the numbers you type never leave your device.

Results are estimates for general information. For medical, legal, structural or financial decisions, confirm with a qualified professional.