Gable Fan CFM Calculator
Powered gable-mounted attic exhaust fan sizing.
Enter your values
Enter the attic floor area in sq ft.
Choose one of: Mild climate (2 CFM/sq ft), Hot climate or dark roof (3 CFM/sq ft).
Results update instantly as you type — no submit needed. Your values are remembered on this device, and the shareable link reopens the calculator with exactly these numbers.
- Required fan airflow
- 4,500 CFM
- Rate used
- 3 CFM/sq ft
- Intake NFA needed
- 15 sq ft (at ~300 CFM per sq ft NFA)
- Note
- A powered gable fan can depressurise the attic and pull conditioned air up if soffit intake is inadequate
Quick answer
Powered gable attic fans are commonly sized at 2-3 CFM per square foot of attic floor area, higher in hot climates or dark roofing.
CFM = attic area x rate
At a glance
| What it does | Powered gable-mounted attic exhaust fan sizing. |
|---|---|
| Category | HVAC & Airflow |
| Inputs needed | Attic floor area, Climate / roof |
| Main output | Required fan airflow |
| Formula | CFM = attic area x rate |
| Cost | Free — no sign-up, no download |
How to use the Gable Fan CFM Calculator
- 1Measure the attic floor area.
- 2Choose a rate based on climate and roof colour.
- 3Ensure soffit or other intake vents provide enough net free area so the fan does not pull air from the living space instead.
Inputs explained
- Attic floor area(sq ft)
- Enter the attic floor area in sq ft.
- Climate / roof
- Choose one of: Mild climate (2 CFM/sq ft), Hot climate or dark roof (3 CFM/sq ft).
Worked example
Using the values the calculator loads with:
Inputs
- Attic floor area1500 sq ft
- Climate / roofHot climate or dark roof (3 CFM/sq ft)
Results
- Required fan airflow4,500 CFM
- Rate used3 CFM/sq ft
- Intake NFA needed15 sq ft (at ~300 CFM per sq ft NFA)
- NoteA powered gable fan can depressurise the attic and pull conditioned air up if soffit intake is inadequate
Frequently asked questions
Are powered attic fans still recommended?
Many building scientists now favor sealed, well-insulated attics over powered fans, since fans can worsen air leakage from below if not matched with soffit intake.
Ridge vent vs gable fan?
A continuous ridge vent with soffit intake is passive and often preferred; a gable fan is an active alternative for attics without good ridge venting.
What do I need to enter into the Gable Fan CFM Calculator?
Just 2 values: attic floor area, climate / roof. Every field starts with a realistic example, so you can change one number at a time and watch the result update instantly.
How does the Gable Fan CFM Calculator work out the answer?
Powered gable attic fans are commonly sized at 2-3 CFM per square foot of attic floor area, higher in hot climates or dark roofing. It applies the formula CFM = attic area x rate and shows the working so you can check each step by hand.
Is the Gable Fan CFM Calculator free, and do I need an account?
It is completely free with no sign-up, no download and no usage limit. Everything is calculated in your browser, so the numbers you type never leave your device.