HVAC & Airflow

Spray Booth Filter Velocity Calculator

Filter face velocity for paint booth intake or exhaust filters.

Enter your values

Enter the booth airflow in CFM.

Enter the filter bank width in ft.

Enter the filter bank height in ft.

Results update instantly as you type — no submit needed. Your values are remembered on this device, and the shareable link reopens the calculator with exactly these numbers.

Results
Filter face velocity
104 FPM
Filter area
96 sq ft
Typical limit
100-150 FPM
Status
Within typical limit

Quick answer

Paint booth filters typically need to stay under about 100-150 FPM face velocity to maintain arrestance efficiency and acceptable pressure drop.

Velocity = CFM / filter area

At a glance

What it doesFilter face velocity for paint booth intake or exhaust filters.
CategoryHVAC & Airflow
Inputs neededBooth airflow, Filter bank width, Filter bank height
Main outputFilter face velocity
FormulaVelocity = CFM / filter area
CostFree — no sign-up, no download

How to use the Spray Booth Filter Velocity Calculator

  1. 1Enter the booth's design airflow.
  2. 2Enter the filter bank's width and height.
  3. 3Compare the resulting face velocity to the filter manufacturer's rated maximum.

Inputs explained

Booth airflow(CFM)
Enter the booth airflow in CFM.
Filter bank width(ft)
Enter the filter bank width in ft.
Filter bank height(ft)
Enter the filter bank height in ft.

Worked example

Using the values the calculator loads with:

Inputs

  • Booth airflow10000 CFM
  • Filter bank width12 ft
  • Filter bank height8 ft

Results

  • Filter face velocity104 FPM
  • Filter area96 sq ft
  • Typical limit100-150 FPM
  • StatusWithin typical limit

Frequently asked questions

What if velocity is too high?

Add filter area (larger bank or additional stages) or reduce fan airflow to protect filter life and capture efficiency.

Does loaded filter velocity change?

As filters load with paint, resistance rises and actual velocity through clean areas increases — monitor with a manometer.

What do I need to enter into the Spray Booth Filter Velocity Calculator?

Just 3 values: booth airflow, filter bank width, filter bank height. Every field starts with a realistic example, so you can change one number at a time and watch the result update instantly.

How does the Spray Booth Filter Velocity Calculator work out the answer?

Paint booth filters typically need to stay under about 100-150 FPM face velocity to maintain arrestance efficiency and acceptable pressure drop. It applies the formula Velocity = CFM / filter area and shows the working so you can check each step by hand.

Is the Spray Booth Filter Velocity Calculator free, and do I need an account?

It is completely free with no sign-up, no download and no usage limit. Everything is calculated in your browser, so the numbers you type never leave your device.

Results are estimates for general information. For medical, legal, structural or financial decisions, confirm with a qualified professional.